No piece of land shall be used as a site
for the construction of building;
- If the Authority considers that the site is in sanitary or that
it is dangerous to construct a building on it;
- If the site is within a distance or 9m from the edge of water
mark of a minor water course and 15m. from the edge of water mark
of a major water course, provided that where a water course passes
through a low lying land without any well defined banks, the owner
of the property may be permitted by the Authority to restrict or
divert the water course to an alignment and cross section as
determined by the Authority.
- If the site is not drained properly or is incapable of being
well drained;
- If the owner of the building has not shown to the satisfaction
of the authority all the measures required to safeguard the
construction from constantly getting damp;
- If the building is for assembly uses, for cinemas and theatres
as well as for public worship which has not been previously
approved by the Authority;
- If the building is proposed on any area filled up with
carcasses, excreta, filthily and offensive matter till the
production of certificate from the Authority to the effect that it
is safe from the health and sanitary point of view, to be built
upon;
- If the use of the said site is for the purpose, which in
the opinion of the Authority will be a source of annoyance to the
health and comfort of the inhabitants of the neighbourhood;
- If the plot has not been approved as a building site by the
Authority;
- If the proposed occupancy of the building on the site does not
conform to the land use proposals in the development plans or
Zoning Regulations; and
- If the level of the site is less than prescribed datum level
depending on topography and drainage aspects.
|
Distance of Site from Electric Lines -
No Verandah, balcony or the like shall be allowed to be erected or
re-erected or any additions or alternations made to a building on a site
within the distance quoted in Table No.3 below in accordance with the
prevailing Indian Electricity Rules and its amendments from time to time
between the building and any overhead electric supply line;
TABLE NO.3
| |
Vertically
m |
Horizontally
m |
| Low and medium voltage
lines and service lines. |
2.5 |
1.2 |
| High voltage lines
up to and including 33,000 V. |
3.7 |
2.0 |
| Extra High voltage
beyond 33,000 V. |
3.7 |
2.0 |
| |
(plus 0.3
m for every additional 33,000 V or part thereof) |
(plus 0.3
m. for every additional 33,000 V or part thereof) |
|